Ground fault protector/earth leakage protector for Series G E
Instructional Leaflet IL01202012E
Effective October 2010
Ground fault protector/earth leakage protector
for Series G E-Frame circuit breakers and
HMCPE motor circuit protectors
El protector de fallas a tierra/protector de fugas a tierra para interruptores
de circuito Serie G Marco-E y protectores de motores HMCPE
 WARNING
 ADVERTENCIA
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON
EQUIPMENT WHILE IT IS ENERGIZED. DEATH, SEVERE PERSONAL
INJURY, OR SUBSTANTIAL PROPERTY DAMAGE CAN RESULT FROM
CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO
VOLTAGE IS PRESENT BEFORE PROCEEDING.
NO INTENTE INSTALAR O LLEVAR A CABO TRABAJOS DE
MANTENIMIENTO EN EL EQUIPOMIENTRAS TENGA ENERGIA.
EL CONTACTO CON EQUIPO CON ENERGIA PUEDE PROVOCAR LA
MUERTE O LESIONES PERSONALES SEVERAS. ANTES DE PROCEDER,
VERIFIQUE SIEMPRE QUE NO HAYA VOLTAJE PRESENTE.
Insert Unit Into Breaker.
Attach Endcap.
Maximum Breaker Rating
125A Continuous.
Coloque la unidad en el interruptor.
Reset Unit
Coloque la tapa
en el extremo.
Denominación máxima
del interruptor 125A
continuo.
Figure 1.
Figure 3.
Tighten Breaker Screws.
Insert Screws
and Washers.
Apriete los tornillos del interruptor.
Inserte los tornillos
y arandelas
dentro de los
retenedores.
0.156 in
(3.97mm)
0.156 pulg.
A_1
A_1
A_1
A_1
34–38 in lb
(3.8–4.3 Nm)
34–38 pulg./lb.
Figure 2.
Figure 4.
Instructional Leaflet IL01202012E
Ground fault protector/earth leakage protector 
for Series G E-Frame circuit breakers and 
HMCPE motor circuit protectors
Effective October 2010
Remove Secondary Cover.
Test by Pushing Push-To-Trip Button.
Remueva la tapa secundaria.
Pruebe la unidad presionado
el boton de disparo.
1
3
2
Figure 5.
Figure 9.
3
Reset Unit and Latch Breaker.
Insert Push Bar into
Mechanical Accessory.
Reinicie la unidad
y cierre el interruptor.
Inserte la barra en
el accesorio mecánico.
2
Figure 6.
1
Figure 10.
Insert Push Bar into RCD Window and
Rotate Mechanical Accessory into Pocket.
Attach Accessories.
Coloque los accesorios.
Inserte la barra en la ventana
del RCD y rote el accesorio dentro
de la cavidad (abertura).
Customer Provided Contact.
Bell Alarm
(3A–250V~)
White
White
Black
50% IG
(0.1A–250V~)
Remote Trip
(0.1A–250V~)
Accessory
Wires
Figure 11.
Figure 7.
Replace Secondary Cover,
Reset Unit and Latch Breaker.
Reemplace la tapa secundaria
y opere el interruptor.
3
Position of the
Toggle Handle
1
Off/Reset
Apriete los tornillos de la tapa
secundaria a un torque
de 10–13 pulg. lb. (1.1–1.5 Nm).
Figure 8.
On
ON
Tripped
TRIP
Orange Blue Green
Orange Blue Green
State of bell alarm contacts as a function of circuit breaker and protector.
Estado de los contactos de la alarma de timbre como una función
de interruptor de circuito y protector.
Figure 12.
eaton corporation www.eaton.com
Position of the Protector Position of the
Reset Button (Yellow)
Protector Bell Alarm
Orange Blue Green
ON
2
Torque Secondary Cover Mounting
Screws 10–13 in lb (1.1–1.5 Nm).
2
Black
Green
Blue
Orange
Contacto provisto por el cliente.
Instructional Leaflet IL01202012E
Ground fault protector/earth leakage protector 
for Series G E-Frame circuit breakers and 
HMCPE motor circuit protectors
50% IG (or 50% I n)
(Indicates 50% of Leakage Value has Been Reached)
Test Button
Boton de prueba
50% IG (o 50% I n)
Indica que 50% del valor defuga fue alcanzado)
Status Light
(Flashes to
indicate proper
operation)
Push-to-Trip
Button
Boton de disparo
C.B. Acc.
560U
Ground Fault Protector
Cat. ELEBN4125W
S# 68D3907G03
Terminal Block
Access
(4-Pole Only)
Acceso al bloque
de terminal
(4 polos solamente)
STATUS
50% IG
TEST
Push
to
Trip
RESET
IG (A)
t(s)
0.15
0.06
0.3
0.3
0.5
Inst.
1
0.1
3
0.03
1
10
NOTICES:
- Terminals if used must be aluminum
0.03
Inst.
TA125EF or TA150EF (Al/Cu).
- See breaker for terminal torque.
- See instrction sheet for high voltage tests.
- For use on Seres G, E-Frame Circuit Breaker, Switch, Motor Circuit Protector.
WARNING
Hazardous voltage – can cause severe
injury or death. In reverse-feed applications
GFP (Ground Fault Protector) is energized
when breaker handle is in any position.
Disconnect all power before installing
or removing GFP.
Do not remove cover from GFP.
t(s) (o  t)
Adjustment
CU-A L
68 C3733 H04
Reset Button
Boton de reinicio
In 125A
4 POLE
120–480 VΣ
50/60 Hz
Class 1
Luz para
indicacion
del estado
(Parpadea
para indicar
operacion
apropiada)
IG (or In)
Adjustment
Adjuste del
IG (o I n)
Adjuste de
t(seg.) (o  t)
Figure 13.
Product operation
1. Earth leakage detected
a. 50% Earth Leakage setting detected, LED and contacts
change state.
b. 100% Earth Leakage setting detected, the module
trips the circuit breaker via mechanical interlock.
c. Reset button on earth leakage module extends,
indicating trip due to earth leakage current.
d. Bell Alarm Auxiliary NO/NC contact in module
changes state.
2. Reset
a. Depress Reset button on module (if tripped on earth
leakage). This will reset the mechanical interlock
allowing the circuit breaker to be reset.
b. Reset circuit breaker.
Effective October 2010
Operación del producto
1. Falla a tierra detectada
a. Se detecta 50% de Falla a Tierra, el LED y contactos
cambian de estado.
b. Se detecta 100% de Falla a Tierra, el modulo dispara
el interruptor de circuito por medio del enlace mecánico.
c. El botón de reajuste en el modulo de fallo a tierra
se extiende, indicando que hubo un disparo debido
a un fallo de corriente a tierra.
d. El contacto en el modulo Alarma de Campana Auxiliar
NO/NC cambia de estado.
2. Reajustar
a. Presione el botón de reajuste en el modulo (si se disparo
debido a falla a tierra). Esto reajustara el enlace mecánico
lo que permitirá que el interruptor de circuito pueda ser
reajustado.
b. Reajustar el interruptor de circuito.
3. Prueba de operación
(el voltaje de línea debe de estar presente)
a. Presione el botón de prueba para probar el circuito
de fallo a tierra.
b. El modulo dispara el interruptor de circuito por medio
del enlace mecánico.
c. El botón de reajuste en el modulo de fallo a tierra
se extiende.
d. El contacto en el modulo Alarma de Campana Auxiliar
NO/NC cambia de estado.
4. Disparo remoto del interruptor de circuito
a. Señal energizada suplida por el cliente
(contacto seco cercano).
b. El modulo dispara el interruptor de circuito por medio
del enlace mecánico.
c. El botón de reajuste en el modulo de fallo a tierra
se extiende.
d. El contacto en el modulo Alarma de Campana Auxiliar
NO/NC cambia de estado.
Table 1a. EG-Frame Line and Load Terminations
Wire Size
Torque
mm2
Terminal
Materials
Catalog
Number
Lb In
2.5–6
Aluminum
TA125EF a
35
4.0
16–95
Aluminum
TA150EF
80
9.0
Frame
Type
Wire
Type
AWG
a. Depress test button to test earth leakage circuit.
EG-Frame
Cu/Al
14–10
b. The module trips circuit breaker via mechanical interlock.
EG-Frame
Cu/Al
6–3/0
c. Reset button on earth leakage module extends.
a Standard collars mounted on ground fault/earth leakage.
d. Bell Alarm Auxiliary NO/NC contact in module
changes state.
Table 1b. Terminaciones de línea y carga del marco EG
3. Test operation (line voltage must be present)
Tamano
de Alambre
4. Remote tripping of breaker (line voltage must be present)
a. Customer-supplied signal energized (dry contact closer).
Tipo de
Marco
Tipo de
Alambre AWG
b. The module trips the circuit breaker via
mechanical interlock.
Marco EG
Cu/Al
14–10
Marco EG
Cu/Al
6–3/0
c. Reset button on earth leakage module extends.
d. Bell Alarm Auxiliary NO/NC contact in module
changes state.
Nm
Torosion
mm
Material de
la terminal
Numero de
catalogo
Lb In
Nm
2.5–6
Aluminio
TA125EF a
35
4.0
16–95
Aluminio
TA150EF
80
9.0
2
a Conectores estándares montados en el dispositivo falla a tierra/fuga a tierra.
eaton corporation www.eaton.com
3
Instructional Leaflet IL01202012E
Ground fault protector/earth leakage protector 
for Series G E-Frame circuit breakers and 
HMCPE motor circuit protectors
Effective October 2010
10.26
(260.6)
0.50
(12.7)
1.00
(25.4)
2.00
(50.8)
3.98 (101.1) Four-Pole
2.98 (75.7) Three-Pole
1.49
(37.8)
0.97
(24.6)
3.81
(96.8)
8.59
(218.2)
2.96
(75.2)
2.90
(73.7)
2.74
(69.6)
2.75
(69.9)
3.01
(76.5)
3.54
(89.9)
3.58
(90.9)
10.26
(260.6)
5.50
(139.7)
1.00
(25.4)
3.00
(76.2)
2.00
(50.8)
1.49 3.98 (101.1) Four-Pole
(37.8) 2.98 (75.7) Three-Pole
0.97
(24.6)
3.81
(96.8)
8.59
(218.2)
Figure 14.
Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2010 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. IL01202012E H01 / Z10486
October 2010
PowerChain Management is a registered
trademark of Eaton Corporation.
All other trademarks are property of their
respective owners.

Documentos relacionados