1 Motor Circuit Protector, Frame JG, LG

Transcripción

1 Motor Circuit Protector, Frame JG, LG
s
Euro Order No.
U.S. Cat. No.
3VL4140-2KK30-0AA0
3VL4140-2KJ30-0AA0
3VL4860-2KJ30-0AA0
3VL4860-2KK30-0AA0
Item: HJM3M400
HJM3L400
HLM3L600
HLM3M600
Motor Circuit Protector, Frame JG, LG
Protector Del Circuito Del Motor, Caja Base JG, LG
Protecteur De Circuit De Moteur, de Base JG, LG
Installation Instructions / Instructivo de Instalación
Hazardous Voltage.
Will cause death or serious injury.
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Tension dangereuse.
Danger de mort ou risque de blessures graves.
Turn off and lock out all power supplying this device before Desenergice totalmente antes de instalar o darle servicio.
working on this device.
Reemplace todas las barreras y cubiertas antes de
Replace all covers before power supplying this device is
energizar el interruptor.
turned on.
Couper l'alimentation de l'appareil et barrer avant de
travailler.
Remplacez touts les couverts avant que
l'approvisionnement de pouvoir soit alimenté.
Use only with Siemens certified Components.
Utilizar únicamente con componentes certificados de Siemens.
A utiliser uniquement avec les composants certifiés Siemens.
NOTE - These instructions do not purport to cover all details or
variations in equipment, or to provide for every possible contingency
to be met in connection with installation, operation or maintenance.
Should further information be desired or should particular problems
arise, which are not covered sufficiently for the purchaser’s purposes,
the matter should be referred to the local Siemens sales office. The
contents of this instruction manual shall not become part of or modify
any prior or existing agreement, commitment or relationship. The
sales contract contains the entire obligation of Siemens. The warranty
contained in the contract between the parties is the sole warranty of
Siemens. Any statements contained herein do not create new
warranties or modify the existing warranty.
Trademarks - Unless otherwise noted, all names identified by ® are
registered trademarks of Siemens AG or Siemens Industry, Inc. The
remaining trademarks in this publication may be trademarks whose
use by third parties for their own purposes could violate the rights of
the owner.
7/16“
10mm
Ø = .28“
[ Ø = 7.1 ]
Cal. ISO 6789
1/4 – 20UNC X 4.0
MSKL4
HJM3M400
HJM3L400
HLM3L600
HLM3M600
1
Trip
[ Interrumpir ]
M6 X 100MM
3VL9500-8SA40
3VL4140-2KK30-0AA0
3VL4140-2KJ30-0AA0
3VL4860-2KJ30-0AA0
3VL4860-2KK30-0AA0
1/3
8 0 6 9 5 4 A 0 3
I.L. No. 806954A03
2
3
1/4 -20UNC
M6
7/16“
10mm
35 lb. in.
[ 4 Nm ]
”
- .20
.08 mm ]
5
[2-
U.S. Cat. No.
4 X 1/4 – 20UNC x 4.00”
MSKL4 - ( 3 + 4 Pole / Polos )
3VL9460-8SB41
2/3
Euro Order No.
4 X M6 X 100mm
3VL9500-8SA40 - ( 4 Pole / Polos )
JG / LG
EX: HLM3M600
[ 3VL4860-2KK30-0AA0 ]
VL Motor Circuit Protector ( MCP )
Motor Full Load Amps
Trip Switch Setting ( A )
96 - 139
115 - 167
135 - 194
154 - 222
173 - 250
192 - 278
154 - 222
185 - 267
215 - 311
246 - 356
277 - 400
( 308 - 400 ) See Footnote 1
154 - 222
185 - 267
215 - 311
246 - 356
277 - 400
308 - 444
212 - 306
254 - 367
296 - 428
338 - 489
381 - 550
423 - 600
1250
1500
1750
2000
2250
2500
2000
2400
2800
3200
3600
4000
2000
2400
2800
3200
3600
4000
2750
3300
3850
4400
4950
5500
Catalog Number
HJM3L400
[ 3VL4140-2KJ30-0AA0 ]
400 Amp
HJM3M400
[ 3VL4140-2KK30-0AA0 ]
400 Amp
HLM3L600
[ 3VL4860-2KJ30-0AA0 ]
600 Amp
HLM3M600
[ 3VL4860-2KK30-0AA0 ]
600 Amp
1 -These settings are provided for starting currents greater than 11X but not to
exceed 17X.
Full Load Amps ( FLA ) not to exceed ampere rating of MCP.
For Support in Europe refer to :
Bestell-Nr. / Order No.: 3ZX1012-0VL68-3BA1
Technical Support:
Subject to change without prior notice
Siemens Industry, Inc. , Norcross, GA 30092 U.S.A.
Internet: www.siemens.de/lowvoltage/technical-assistance
Toll Free: 1-800-241-4453
GWA 4NEB 179 6954-10 DS 04
Internet: www.usa.siemens.com/powerdistribution
© Siemens Industry Inc. 2010
3/3
806954A03

Documentos relacionados

Mounting Screw Kit

Mounting Screw Kit Replace all covers before power supplying this device is energizar el interruptor. turned on.

Más detalles