220kW agenitor 206 Natural Gas

Transcripción

220kW agenitor 206 Natural Gas
2G. Technical Specifications
agenitor 206 (220 kW)
Natural Gas
2G. Combined Heat & Power.
agenitor 206_60Hz/480V
Picture: symbolic - may deviate from module described
Compact CHP module ready for connection,
Integrated heat recovery system assembly,
mainly consisting of
- Gas-Otto-engine from industrial series production
- air-cooled, self-excited, brushless synchronous generator
mainly consisting of
- expansion tank for engine and mixture cooling circuit
- exhaust gas heat exchanger integrated in primary cooling
water circuit
- safety valve in engine, mixture and heating circuit
- filling, drain and bleeding valves
- oxidizing catalyst integrated in exhaust gas heat exchanger
- transfer plate heat exchanger
- pumps for engine, mixture and heating circuit
- oil reservoir with automatic oil top-up device
- 3-way mixing valve for return temperature increase
- control cabinet with programmable logi control and
operating panel
- gas pressure regulation and safety ramp
Water and gas connections are equipped with compensators. All water-side connections above the heat recovery assembly
are directed upwards.
Engine and alternator are linked by a pluggable elastic metal-plastics coupling to compensate radial, axial and angular misalignment and
mounted on vibration damping elements on the module base frame.
Moreover the module base frame is isolated from the installation surface by anti-oscillation elements.
The control cabinet is executed as a separate unit. All regulation and control functions as well as operational controls are integrated.
The menu-navigated touch-screen allows to read and adjust all performance and status data.
The CHP module is driven by a water-cooled, supercharged Gas-Otto engine designed for stationary continuous operation.
The microprocessor-controlled ignition system ensures the optimal adaption of ignition timing and energy to the gas quality (methane no.).
Lambda control is carried without lambda probe by using a calculation program, which sets the optimal lambda value for every
operational status based on actual power, charging pressure and mixture temperature.
The twin-stage mixture cooling with low and high temperature circuit ensures an exceptionally high electrical efficiency as well as
an optimal utilization of thermal power of the mixture heat.
The oil level control is carried out by a sight glass connected to the oil pan with low oil level indication. A 35 liters oil reservoir ensures
automatic oil topping-up between oil changing intervals.
The program especially developed by 2G renders possible oil changing intervals > 2.000 operating hours based on the observance
of 2G's oil limit values as per technical instruction "2G TA10 AGENITOR Oil" which were determined through specific long term tests.
Technical specification agenitor 206 natural gas_60Hz/480V - D 440
14.11.2012 (PNI, HHE)
Version 1.4
1-3
Engine data
Hz
Mixture cooling to
60
Engine utilities
°F
122
Specific lubricating oil consumption
g/kWh
0,2
Nominal speed
rpm
1800
Filling capacity lubricating oil min./max.
U.s. gal
8 / 11
ISO standard power (mech.)
kW
231
Stoichiometric ratio (Lambda)
λ
Filling capacity cooling water
U.s. gal
1,6
Row
Arrangement of cylinders
Operating pressure (max.)
psi
Cooling water flow
gpm
74
5,04
Cooling water temperature min.
°F
176
in
6,54
Cooling water temperature max.
°F
190
l
12,82
Difference (inlet/outlet max.)
K
6
Mixture inlet temperature after throttle valve max.
°F
122
Mixture cooling water inlet temperature.
°F
113
gpm
23
°F
185
gpm
31
6
Number of Cylinders
Bore
in
Stroke
Engine displacement
Sense of rotation (viewing on flywheel)
left
Housing of flywheel
SAE 1
Tooth rim with number of teeth
Z
160
Compression ratio
ε
13.5 : 1
Mean effective pressure
psi
173,9
Mixture cooling water inlet temperature
average piston speed
ft/s
27,2
high temperature circuit (max.)
Power data
Hz
60
high temperature circuit (max.)
Efficiencies
low temperature circuit (max.)
Mixture cooling water flow
low temperature circuit (max.)
Mixture cooling water flow
Load
4
29
%
100
°BTDC
20
ISO standard power (mech.)
kW
231
Electrical
%
38,2
Electrical Power
kW
220
Mechanical
%
40,0
Cooling water heat
kW
101
Thermal
%
45,7
Mixture heat (high temperature circuit)
kW
21
Total (el. + th.)
%
83,9
Mixture heat (low temperature circuit)
kW
16
Exhaust gas heat down to 248 °F
kW
141
Useable thermal power at 248 °F exhaust gas
kW
263
Heat radiation of module (max.)
kW
38
Fuel power (consumption)
kW
576
Ignition timing BTDC
Electrical-thermal power ratio
0,84
Mass and volume flows
Specific fuel consumption (mech.)
kWh/kWh
Combustion air mass flow
lb/h
Specific fuel consumption (el.)
kWh/kWh
Combustion air volume flow
cfm
2.515
567
Inlet air volume flow (max.)
cfm
5.102
Fuel mass flow
lb/h
99
Fuel volume flow
cfm
33
Temperatures and pressures
Exhaust gas temperature after turbine
°F
923
Exhaust gas back pressure (max.)
psi
0,435
Exhaust gas mass flow, wet
lb/h
2.614
Heating water return temperature (max)
°F
158
Exhaust gas mass flow, dry
lb/h
2.450
Heating water header temperature (max)
°F
194
Exhaust gas volume flow, wet
cfm
550
Pressure loss heating circuit (max)
psi
2,18
Exhaust gas volume flow, dry
cfm
487
Under pressure at the air intake (max)
psi
0,22
Heating water volume flow (max.)
gpm
66
Emission values at 5% residual oxygen and dry exhaust gas
NOx
CO
Technical basic conditions
g/bhp-hr
< 1.0
Standard reference conditions acc. to DIN-ISO-3046/I
ppm
< 91
< 0.6
< 90
Air pressure: 14.5 psi,
g/bhp-hr
ppm
Air temperature: 77 °F, rel. Humidity: 30%.
Gas quality according "2G TA 04 Gas Quality"
All data are referred to engine full load at the indicated media
temperatures and are subject to technical progress. Operating
media and balance of plant have to be carried in accordance with
2G's technical instructions. Power reduction due to installation
at altitude <400m a.s.l. and/or air suction temperature <30°C
shall be specifically determined for each project.
Technical specification agenitor 206 natural gas_60Hz/480V - D 440
14.11.2012 (PNI, HHE)
Version 1.4
2-3
Alternator data
Main dimensions and weights
Manufacturer
Leroy Somer
Type
Module:
LSA 46.2 VL12
Length (L):
in
146
kVA
275
Height (H):
in
87
Voltage
V
480
Width (B):
in
51
Frequency
Hz
60
Weight (approx.)
lb
7.716
1/min
1800
Nominal power at cos φ = 0,8
Nominal speed
Nominal current at Cos φ = 0,8
A
Cos φ
331
Control switchboard
Height (H)
in
83
Efficiency (full load) at Cos φ = 1
%
95,40
Width (B)
in
39
Efficiency (full load) at Cos φ = 0,8
%
94,00
Depth (T)
in
24
Reactance X"d
%
8,80
Weight (approx.)
lb
441
%
9,90
kg m²
2,80
Power switchboard
Star
Height (H)
in
79
104
Width (B)
in
24
IP 23
Depth (T)
in
20
Weight (approx.)
lb
331
Reactance Xi = X2
Mass moment of inertia
Stator circuit
Ambient air temperature
°F
Protection class
0.8 - 1
Cos φ shall be between 0,8 and 1,0 over the entire power range.
Modul:
Control switchboard
Technical specification agenitor 206 natural gas_60Hz/480V - D 440
14.11.2012 (PNI, HHE)
Version 1.4
Power switchboard
3-3